Testing of low-voltage switchgear and low-voltage/medium-voltage power distribution systems
| High current
tests |
 |
| • |
Short-circuit, making and breaking capacity
AC 3-ph. up to 300 kA at 50 Hz
AC 3-ph. up to 200 kA at 60 Hz
DC up to 37 kA |
| • |
Short-time withstand current
AC 3ph. up to 120 kA at 1 s
AC 3ph. up to 65 kA at 3 s |
| • |
Internal arc test
|
Heating
tests up to 12 kA |
Tripping
behaviour up to 25 kA |
Performance
tests
|
 |
Insulation tests |
Mechanical durability |
Electrical
durability up to 1,2 kA AC-1
Electrical durability
up to 6,2 kA AC-3
and AC-4 |
Degree of
protection (IP-code) up to IP 6X and
IP X9K |
Mechanical
properties of terminals |
Vibration
and shock tests
|
Climatic
tests
|
|
 |
 |
|
|
|